資源描述:
《邁凱德臨時用電方案》由會員上傳分享,免費在線閱讀,更多相關(guān)內(nèi)容在行業(yè)資料-天天文庫。
1、山東邁凱德10萬噸/年硝酸異辛酯儲罐制安臨時用電施工方案ZC/C工安-053-2014山東淄建集團工業(yè)設(shè)備安裝分公司2014年08月施工方案審核意見記錄表工程名稱山東邁凱德節(jié)能科技有限公司10萬噸/年硝酸異辛酯項目施工組織設(shè)計或施工方案名稱及編號10萬噸/年硝酸異辛酯項目臨時用電施工方案ZC/C工安-053-2014分公司各科室審核意見及簽字技術(shù):質(zhì)量:安全:設(shè)備:工會:年月日分公司技術(shù)負責人意見及簽字目錄1.工程概況··················································12.編制依據(jù)··
2、················································13.施工用電部署··············································14.負荷計算及電氣材料選擇····································25.安全用電技術(shù)措施··········································36.安全用電組織措施··········································67.施工機械設(shè)備總表
3、··········································78.供電系統(tǒng)圖················································89.廠區(qū)平面圖···············································1210.配電系統(tǒng)圖··············································1311.接地系統(tǒng)圖···············································14一、
4、工程概況山東邁凱德10萬噸/年硝酸異辛酯項目立式儲罐制安。工程內(nèi)容為碳鋼儲罐制作安裝:300m3拱頂儲罐,共計18臺。廠區(qū)位于淄博市高新區(qū)傅山鎮(zhèn)北嶺村,北嶺路與寶山東路交匯處,廠區(qū)內(nèi)儲罐施工現(xiàn)場無障礙物,無架空線路。工程施工電源引自甲方廠用配電室,電源電壓380/220V。1.工程名稱:山東山東邁凱德10萬噸/年硝酸異辛酯項目;2.工程地點:淄博市高新區(qū)傅山鎮(zhèn)北嶺村。3.主要施工內(nèi)容:碳鋼儲罐制作安裝300m3拱頂儲罐,共計18臺。二、編制依據(jù)1.10萬噸/年硝酸異辛酯施工方案2.《建設(shè)工程現(xiàn)場供用電安全規(guī)范》GB50194—933.
5、《施工現(xiàn)場臨時用電安全技術(shù)規(guī)范》JGJ46—20054.《建設(shè)施工安全檢查標準》JGJ59—2011三、施工用電部署1.根據(jù)設(shè)備布置及現(xiàn)場條件,我方使用的臨時用電總配電箱從甲方廠區(qū)內(nèi)的配電室引出并置于廠區(qū)東側(cè);分配電箱從我方的的臨時配電總箱中引出,分箱放置在制作罐體附近。用與直流弧焊機、磨光機、空壓機及無齒鋸的供電。(具體布置情況詳見附圖)2.配電方式采用線路埋地敷設(shè)配電,甲方供電方式為三相四線制,甲方配電室至現(xiàn)場總配電箱采用埋地敷設(shè),現(xiàn)場配電總箱至分箱電纜也采用埋地敷設(shè)。3.工程采用TN-S接零保護方式,總配電箱及3個分配電箱共用一
6、組接地裝置并做到三級配電二級保護,接地電阻不大于10Ω,各個分箱另設(shè)重復接地裝置,接地電阻≤10Ω總漏電保護器位于總箱內(nèi),末級漏電保護器位于開關(guān)箱內(nèi),上下級漏電保護器必須匹配,末級漏電保護器漏電動作電流不大于30mA,動作時間≤0.1s。7四、負荷計算及電氣材料選擇施工機械設(shè)備總表序號機械名稱規(guī)格型號功率單位數(shù)量備注1烘干箱202--Ⅳ8KW臺12室內(nèi)照明0.5KW盞63室外照明1KW盞24直流焊機ZX4--40017KVA臺11三相380VCosφ=0.85磨光機SHB--1000.5KW臺86空壓機W—0.9/70.75KW臺17
7、無齒鋸3KW臺14.1總箱Sjs=1.05×(K1∑P1/COSΦ+K2∑S2+K3∑S3+K4∑S4)=1.05×[0.6×(0.75+0.5×6+8+3)/0.7+0.6×(17×11)+0.6x1×5)]=134.23KVAIjs=Sjs/√3×U=203.9A根據(jù)計算結(jié)果,一號總電源電纜3×50+2×16,選總配電箱ZX-7,箱內(nèi)總開關(guān)400A,出線回路漏電斷路器DZ10L—250/4304.2分路負荷計算及電器材料選擇4.2.11#分配電箱回路供直流電焊機4臺、磨光機3臺、空壓機1臺。Sjs=1.05×(0.6×0.5×3/
8、0.7+0.6×17×4+0.5×1)=42.68KVA7Ijs=42.68/(1.732×0.38)=64.86A選電源電纜VV22--3×25+2×16,選分配電箱ZX-5。4.2.22#分配電箱回路:直流電焊機3臺