1、第44卷第504期電測(cè)與儀表Vol.44No.5042007年第12期ElectricalMeasurement&InstrumentationDec.2007典型小電流接地故障實(shí)例及暫態(tài)選線分析*李天友1,王超2,陳敏維3,薛永端2,黃建業(yè)3(1.國(guó)網(wǎng)福建省電力有限公司,福州350003;2.山東科匯電力自動(dòng)化股份有限公司,濟(jì)南250101;3.國(guó)網(wǎng)福建省電力有限公司電力科學(xué)研究院,福州350007)摘要:目前對(duì)小電流接地故障特征的理論分析已較完善,但缺乏對(duì)現(xiàn)場(chǎng)典型小電流接地故障實(shí)例的認(rèn)識(shí)及利用典型實(shí)例對(duì)選線技術(shù)的驗(yàn)證。本文介紹了暫態(tài)選
2、線方法及原理,并根據(jù)現(xiàn)場(chǎng)選線裝置實(shí)際記錄的典型故障實(shí)例波形,分析并總結(jié)了典型接地故障的發(fā)生原因、故障特征及對(duì)暫態(tài)選線結(jié)果的影響。通過對(duì)現(xiàn)場(chǎng)典型小電流接地故障實(shí)例的分析與總結(jié),有利于提高對(duì)現(xiàn)場(chǎng)典型接地故障特征的認(rèn)識(shí),驗(yàn)證暫態(tài)選線裝置的可靠性。關(guān)鍵詞:小電流接地系統(tǒng);單相接地故障;典型實(shí)例;暫態(tài)選線中圖分類號(hào):TM933文獻(xiàn)標(biāo)識(shí)碼:B文章編號(hào):1001-1390(2018)00-0000-00Analysisoftypicalsingle-phaseearthfaultsexampleandtransientfaultyfeederselec
3、tiontechnologyinthenon-solidlyearthedsystemLiTianyou1,,WangChao2,ChenMinwei3,XueYongduan4,HuangJianye3(1.StateGridFujianElectricPowerCo,,Ltd.,Fuzhou350003,China.2.ShandongKehuiPowerAutomationCo.,Ltd.,Ji’nanJinan250101,China,China.3.State3.ElectricPowerResearchInstituteSta
4、teGridFujianElectricPowerCompanyElectricPowerResearchInstitute,Fuzhou350007,China)Abstract:Thefaultcharacteristictheoreticalanalysisinthenon-solidlyearthednetworkisalmostcomplete.ButWhiletheunderstandingofthetypicalfieldfaultsexampleandtheverificationofthefaultyfeedersele
5、ctiontechnologiesbyfieldfaultsdataareingreatdemand.Themethodandprincipleoftransientfaultyfeederselectiontechnologiesareintroducedinthispaper.Accordingtothetypicalfieldfaultswaveforms,thecauseofthetypicalfieldfaults,thefaultcharacteristicandtheeffectontheresultofthetransie
6、ntfaultyfeederselectiontechnologiesareanalyzed.Byanalyzingandsummarizingthetypicalfieldfaults,examples,theunderstandingofthetypicalfieldfaultscanbeimproved.Thereliabilityofthetransientfaultyfeederselectiontechnologiescanbeverified.Keywords:non-solidlyearthednetwork,single
7、-phasegroundingfault,typicalfieldfaults,transientfaultyfeederselection-1-第44卷第504期電測(cè)與儀表Vol.44No.5042007年第12期ElectricalMeasurement&InstrumentationDec.20070 引言*基金項(xiàng)目:國(guó)家自然科學(xué)基金資助項(xiàng)目(51477184);國(guó)家電網(wǎng)公司科技項(xiàng)目(52130416000D)為提高配電系統(tǒng)的供電可靠性,我國(guó)多采用小電流接地方式[1],包括中性點(diǎn)不接地和諧振接地(中性點(diǎn)經(jīng)消弧線圈接地)。小電流接地系
8、統(tǒng)發(fā)生單相接地故障時(shí)線電壓保持不變,因此系統(tǒng)可繼續(xù)帶故障運(yùn)行一段時(shí)間[2],為防止事故進(jìn)一步擴(kuò)大,需進(jìn)行故障選線并及時(shí)隔離故障。目前各學(xué)者提出了基于穩(wěn)態(tài)和暫態(tài)[3-6]、投切中電阻[7]、基于