1、6SigmaDC:TheOnlyWaytoBuildaSuccessfulModularDataCentreGuyRuddockVP–Design,DeliveryandOperationsDataCentreServices?2010ColtTechnologyServicesGroupLimited.Allrightsreserved.IntroductionCOLT-Don’ttheymakeguns?WhatisaModularDataCentreWhywouldyouwantoneHowdoyougoabout

2、designingoneGoodintheorybutdoesitwork2Backgroundto‘theother’ColtListedontheUKStockMarketRoughly$2bnTurnoverpaMajorshareholder–FidelityOriginallyformedfromtheDevonshireInvestmentsCompanybasedinBoston,MassOriginallycalledColtbecauseofTheCityOfLondonTelecommunicatio

3、nscoltd..Coltbuilds,runsandoperatesover250datacentre/nodesitesacrossEurope?Roughlyequivalentto6%oftheEuropeanmarket3WhatisaModularDataCentre?Todayyouhave3ChoicestobuildyourDataCentreTraditionalContainerModularAndtheyarealldifferent!4TraditionalBuilds–HaveaLargeOn

4、-SiteTeam5TheTraditionalSolutionAdvantagesDisadvantages6Containerisation–Arrivesquickly,needsutilities,lacksacertainsomething###..7TheContainerSolutionDeliveredtositeworking,onceconnectedtopower/utilitiesAdvantagesDisadvantages8ColtModular–TraditionalDataCentresB

5、uiltinafarmoreeffectiveway9TheModularSolutionAnAllInclusiveDataCentredeliveredtositefullyoperationalAdvantagesDisadvantages10Becareful-notallModularDataCentresarethesame11Awayforward-BacktoFirstPrinciplesCustomerneedsCommonSuppliersneedsOperationalneedsModernData

6、CentreOptimalDesignSensibleBuildCostsReasonablespaceSimplifiedReliabilityCommissioningReducedBuildRiskGoodResilienceEarlyaccesstothehallsEnvironment?LowEmissions?HighCoolingEfficiency12Designingwithmodularityprinciples#..Fora5000sqftfloorarea,ifwetransportitbyroa

7、d,itneededtobebuiltinsectionsDatahallsectionsSwitchgearGenerators13The‘AsBuilt’BaseSpecificationA5000sqft,750KWhallat160w/ft2,PUE1.214x850kvaGeneratorsN+NN+2RoomCoolingN+NSwitchgearUPS12*(N+N),eachUPSsupports64kWoftechnicalloadN+Nfueltanksprovisionedtosupplyfor72

8、hoursrunningatfullloadFlexibleapproachtodeliveringdifferentpowerdensitiesifrequiredDirectandIndirectFreshaircoolingwithvariablecompressorspeedDXbackup8,200hour